Inverter Output Shutoff - Mitsubishi Electric FR-F820-00046 Instruction Manual

Fr-f800 series
Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

*3
The setting is available for the standard structure model and the IP55 compatible model.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• The priorities of the speed commands are defined as follows: JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the Inverter run enable (X10) signal is not assigned, or when the PU operation external interlock (X12) signal is not
assigned while Pr.79 Operation mode selection = "7", the MRS signal performs the same function.
• The same terminals are used to assign the multi-speed (7-speed) setting and the remote setting. The multi-speed setting and
the remote setting cannot be assigned separately.
• When the terminal assignment is changed using Pr.178 to Pr.189 (Input terminal function selection), wiring may be
mistaken due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming
the function of each terminal.
 Adjusting the response of input terminals (Pr.699)
• Response of the input terminals can be delayed in a range between 5 to 50 ms. (The following is the operation example
of the STF signal.)
ON
STF
Pr.699
9999
Pr.699
NOTE
• The Pr.699 setting is invalid (no filter) for the following signals.
— Input signals which are already in the ON state when the power is turned ON
— Input signals used for the PLC function
— Inverter run enable (X10) signal
5.9.9

Inverter output shutoff

The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be selected.
Pr.
Name
17
MRS input selection
T720
 Output shutoff signal (MRS signal)
Output frequency
ON
MRS signal
STF (STR)
ON
signal
• When the Output stop (MRS) signal is turned ON while operating the inverter, the inverter output is instantaneously shut
off.
Time
OFF
Pr.699
Initial
Setting range
value
0
2
0
4
Setting value "0"
Motor coasts
to stop
Time
Description
Normally open input
Normally closed input (NC contact input specification)
External terminal: Normally closed input (NC contact input
specification)
Communication: Normally open input
(Initial
Setting value "2"
value)
Inverter
Inverter
MRS
MRS
SD (PC)
SD (PC)
5.9 (T) Multi-function input terminal parameters
1
2
3
4
5
6
7
8
9
10
357
5. PARAMETERS