Frame A and B
When the voltage of the main power supply is lower than 140 V
models), connect the control power to single-phase UPS or battery.
NOTE:
When EPS is enabled (MI=43):
Do NOT make the fan run in order to prevent voltage drop during EPS.
Parameter settings cannot be saved and will be lost after cycling power.
Set the running speed through Pr.02-23.
Functions of low voltage and phase loss protection are unavailable.
Set the DC bus voltage through Pr.02-21.
DC
Figure 4-6
Figure 4-7
4-7
Chapter 4 WiringEB3000
(230V models) / 280 V
(460V