Chapter 9 Warning and Fault CodesEB3000
Abbreviated
ID No.
Fault Code
55
CE02
Action condition
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Incorrect communication
command from elevator
controller
Malfunction caused by
interference
Different communication
setting from the elevator
controller
Disconnection or bad
connection of the cable
Abbreviated
ID No.
Fault Code
56
CE03
Action condition
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Incorrect communication
command from elevator
controller
Malfunction caused by
interference
Different communication
setting from the elevator
controller
Disconnection or bad
connection of the cable
Display on
Fault Name
KPED-LE02
Communication error 2 Illegal data address
Action and Reset
When the input data address is incorrect
Immediately act
Pr.04-60 (Default: 3)
0: Warn and keep operation
1: Fault and ramp to stop
2: Reserved
3: No action and no display
Auto
When Pr.04-60=0, cE02 is a warning and will be automatically cleared.
Manual When Pr.04-60=1, cE02 is a fault and must be reset manually.
N/A
If cE02 is a warning, it will not be recorded.
If cE02 is a fault, it will be recorded.
Check if the communication command is correct.
Verify the wiring and grounding of the communication circuit. It is recommended to
separate the communication circuit from the main circuit, or wire in 90 degree for
effective anti-interference performance.
Check if the setting for Pr.09-00–Pr.09-02 is the same as the setting for the elevator
controller.
Check the cable and replace it if necessary.
Display on
Fault Name
KPED-LE02
Communication error 3
Action and Reset
When the length of communication data is too long
Immediately act
Pr.04-60 (Default: 3)
0: Warn and keep operation
1: Fault and ramp to stop
2: Reserved
3: No action and no display
Auto
When Pr.04-60=0, cE03 is a warning and will be automatically cleared.
Manual When Pr.04-60=1, cE03 is a fault and must be reset manually.
N/A
If cE03 is a warning, it will not be recorded.
If cE03 is a fault, it will be recorded.
Check if the communication command is correct.
Verify the wiring and grounding of the communication circuit. It is recommended to
separate the communication circuit from the main circuit, or wire in 90 degree for
effective anti-interference performance.
Check if the setting for Pr.09-00–Pr.09-02 is the same as the setting for the elevator
controller.
Check the cable and replace it if necessary.
Corrective Actions
Illegal data value. Occurs when
communication data length exceeds limits.
Corrective Actions
9-36
Description
Description