Chapter 8 Descriptions of Parameter SettingsEB3000
Mains power outage
Automatic Rescue
Device (ARD) is ON
The host sends [EPS
Enable] to [MI=43]
MI=43
Check
Enable
YES
Sends FWD/REV
commands
The elevator
reaches the level
EPS Flow Chart
Disables FWD/REV
commands
The host sends [EPS
Enable] to [MI=43]
ARD is OFF
NO
EPS Flow Chart (ARD or UPS)
8-02-10
The steps to set ARD/UPS as EPS are as
follows:
1.
Set MI = 43 (EPS function)
2.
Set Pr.02-20 = EPS mode selection
3.
Set Pr.02-21 = Emergency power
voltage running
4.
Set Pr.02-22 = Emergency power
capacity running
5.
Set Pr.02-24 = Power generation
direction search time
6.
Set Pr.02-25 = Detecting level of
power factor at the direction of power
generation
NOTE: ARD or UPS can automatically
judge whether to cut off the power or not.