07-33
Cooling Fan Control
VF
Control Mode
Settings
 Use this parameter for the fan control.
 When Pr.07-33 is set to 3 and IGBT temperature is higher than 60°C, the fan starts to run until it
is lower than 40°C.
07-36
Notch Filter Depth
Control Mode
Settings
07-37
Notch Filter Frequency
Control Mode
Settings
 Sets the resonance frequency of the mechanical system. Adjust it to a smaller value to suppress
the mechanical system resonance.
 A larger value improves resonance suppression function.
 The notch filter frequency is the mechanical frequency resonance.
Display Settings
07-40
Start-up Display
VF
Control Mode
Settings
 Determines the start-up display page after power is applied to the drive.
07-41
Content of Multi-function Display
VF
Control Mode
Settings
SVC
FOCPG
0: Cooling fan is always ON.
1: One minute after AC motor drive stops, cooling fan is OFF.
2: AC motor drive runs and cooling fan is ON; AC motor drive stops and
cooling fan is OFF.
3: Cooling fan is ON to run when preliminary IGBT temperature (°C)
reached.
4: Cooling fan is always OFF.
FOCPG
0–20 db
FOCPG
0.00–200.00 Hz
SVC
FOCPG
0: Display the Frequency command value (LED F)
1: Display the actual output frequency (LED H)
2: DC bus voltage (V)
3: Display the output current (A)
4: Output voltage (E)
5: User-defined (see Pr.07-41)
SVC
FOCPG
0: Display the output current supplied to the motor from the drive (A) (Unit:
Amp)
1: Reserved
2: Display the drive's actual output frequency (H) (Unit: Hz)
Chapter 8 Descriptions of Parameter SettingsEB3000
FOCPM
FOCPM
FOCPM
FOCPM
FOCPM
8-07-7
Default: 2
Default: 0
Default: 0.00
Default: 0
Default: 0