Cause
The load is too large
Acceleration time is too
short
The capacity of the drive is
too small
Abbreviated
ID No.
Fault Code
22
EoL1
Action condition
Action time
Fault treatment parameter Stops output immediately, and coasts to stop.
Reset method
Reset condition
Record
Cause
The load is too large
Acceleration time is too
short
When using VFD dedicated
motors, Pr.04-53 setting
(Electronic Thermal Relay)
is incorrect.
Abbreviated
ID No.
Fault Code
24
oH3
Action condition
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Motor locked
The load is too large
Ambien temperature is too
high
Motor cooling system error Check the cooling system to make it work normally.
Motor fan error
Operates at low-speed too
long
Accel./ Decel. time and
working cycle are too short
V/F voltage is too high
when in open-loop circuit
control
Reduce the load.
Adjust acceleration /deceleration time (Pr.00-71–Pr.00-78)
Replace the drive with a larger capacity model.
Display on
Fault Name
KPED-LE02
Electronic thermal relay
1 protection
Action and Reset
150% of the motor's rated current
Electronic Thermal Characteristic (Pr.04-54)
Manual reset
Resets immediately
Yes
Reduce the load.
Adjust acceleration /deceleration time (Pr.00-71–Pr.00-78)
Pr.04-53 Electronic Thermal Relay selection:
0: Standard motor
1: Inverter motor
2: Disabled
Display on
Fault Name
KPED-LE02
Motor over-heating PTC
Action and Reset
PTC input level > Pr.04-51 (default = 50%)
Immediately act
Pr.04-50 PTC (Positive Temperature Coefficient) Detection Action (Default: 0)
0: Warn and keep operation
1: Fault and ramp to stop
Auto
When Pr.04-50=0, oH3 is a warning and will be automatically cleared.
Manual When Pr.04-50=1, oH3 is a fault and must be reset manually.
Resets when PTC input level is lower than [Pr.04-51 – 5].
If oH3 is a warning, it will not be recorded.
If oH3 is a fault, it will be recorded.
Clear the motor lock status.
Decrease the loading.
Replace with a motor with larger capacity.
Change the installed place if there are heating devices in the surroundings.
Install/ add cooling fan or air conditioner to lower the ambient temperature.
Replace the fan.
Decrease low-speed operation time.
Change to dedicated motor for the drive.
Increase the motor capacity.
Increase setting values for Pr.00-71–Pr.00-78 (accel./ decel. time).
Decrease the setting values for Pr.03-51–Pr.03-56 (V/F curve).
Chapter 9 Warning and Fault CodesEB3000
Corrective Actions
Motor overload
Corrective Actions
Motor overheating (PTC) when using a motor
with PTC installed
Corrective Actions
9-27
Description
Description