Appendix B. Modbus ProtocolEB3000
5. Address list
ASCII mode:
 Reads one or more parameter values: 3Ah (start bit':') + 30h 31h (station address 01) + 30h 33h
(function code 03h) + 30h 30h xxh xxh–32h 36h xxh xxh (Modbus address 00xxh–26xxh) + xxh xxh
xxh xxh (reading length 1) + LRC (checksum) + CR/LF
 Writes one parameter value: 3Ah (start bit':') + 30h 31h (station address 01) + 30h 36h (function
code 06h) + 30h 30h xxh xxh–32h 36h xxh xxh (Modbus address 00xxh–26xxh) + xxh xxh xxh xxh
(writing value) + LRC (checksum) + CR/LF
 Writes 20 parameter values: 3Ah (start bit':') + 30h 31h (station address 01) + 31h 30h (function
code 10h) + 30h 30h xxh xxh–32h 36h xxh xxh (Modbus address 00xxh–26xxh) + 30h 30h 31h 34h
(word data length) + 32h 38h (byte data length) + xxh xxh xxh xxh (the first writing value) + ... + xxh
xxh xxh xxh (the 20th writing value) + LRC (checksum) + CR/LF
RTU mode:
 Reads one or more parameter values: 01h (station address 01) + 03h (function code 03h) + 00xxh–
26xxh (Modbus address) + xxxxh (reading length) + CRC (checksum)
 Writes one parameter value: 01h (station address 01) + 06h (function code 06h) + 00xxh–26xxh
(Modbus address) + xxxxh (writing value) + CRC (checksum)
 Writes 20 parameter values: 01h (station address 01) + 10h (function code 10h) + 00xxh–26xxh
(Modbus address) + 0014h (data length, count by word) + 28h (data length, count by byte) + xxxxh (the
first writing value) + ... + xxxxh (the 20th writing value) + CRC (checksum)
AC motor drive parameters (GGnnH): communication station address is Pr.09-00 setting value
Modbus Address
GGnnH
Control command (20xx): communication station address is Pr.09-00 setting value
Function
Modbus
Name
Address
Operation
2000H
command
Attribute (Function Code)
R (03H) / W (06H, 10H)
Attribute
(Function Code)
bit1–0
bit3–2
R (03H) /
W (06H, 10H)
bit5–4
bit7–6
Description
GG means parameter group, nn means parameter number.
For example, the Modbus address of Pr.04-10 is 040AH
when reading by Delta VFDsoft.
Description
00B: No function
01B: Stop
10B: Run
11B: JOG + Run
Reserved
00B: No function
01B: FWD
10B: REV
11B: Change direction
00B: 1st accel. / decel.
B-10
1. Remains the status
specified by a first
command until a second
command is received.
2. Valid only when operation
command source is set to
communication (Pr.00-
03=2).
1. Valid only when 2000h bit12

Advertisement