3. Select the suitable clamps that correspond to the wire size of the shielding cable, and then fix the
clamps using the enclosed screws with the torque value recommended in the table below. Then,
the installation is completed.
Frame
Wire Size
6–8 AWG
60 * 12 * 21.2
A
8–10 AWG
4–6 AWG
67 * 12 * 21.8
B
6–8 AWG
60 * 12 * 21.2
Clamp Size
Screw
M5 * P0.8 * L12
47 * 9 * 14.6
M4 * P0.7 * L12
M4 * P0.7 * L20
M5 * P0.8 * L12
Chapter 11 Optional AccessoriesEB3000
Qty.
4
28–30 kg-cm / (24.30–26.04 lb-in.) / (2.74–2.94 N-m)
4
12–16 kg-cm / (10.42–13.89 lb-in.) / (1.18–1.57 N-m)
4
12–16 kg-cm / (10.42–13.89 lb-in.) / (1.18–1.57 N-m)
4
28–30 kg-cm / (24.30–26.04 lb-in.) / (2.74–2.94 N-m)
11-29
Recommended Torque