Functions
16
Slip error (oSL)
17
Fault indication 1
18
Reserved
19
Brake transistor output error
20
Warning output
21
Over-voltage
Over-current stall prevention
22
warning
Over-voltage stall prevention
23
warning
24
Operation mode indication
25
Forward command
26
Reverse command
27
Output when current ≥ Pr.02-03
28
Output when current < Pr.02-03
29
Reserved
30
Reserved
Power generation direction and
31
status verification
32
Power generation direction
Zero speed (actual output
33
frequency)
Zero speed with stop (actual
34
output frequency)
Fault output option 1 (Pr.02-71)
35
36
Fault output option 2 (Pr.02-72)
37
Fault output option 3 (Pr.02-73)
38
Fault output option 4 (Pr.02-74)
39
Reserved
Speed reached (including zero
40
speed)
41
Reserved
Chapter 8 Descriptions of Parameter SettingsEB3000
Active when the slip error is detected (according to Pr.04-21).
Activate after 10 ms when a fault occurs (except Lv stop).
Active when a brake transistor error is detected
Active when a warning is detected.
Active when an over-voltage is detected. DC bus over-voltage
during acceleration (ovA), DC bus over-voltage during
deceleration (ovd), DC bus over-voltage during constant speed
(ovn), or DC bus over-voltage at stop (ovS).
Active when an over-current stall prevention is detected.
Active when an over-voltage stall prevention is detected.
Active when the operation command is controlled by an external
terminal (Pr.00-03=1).
Active when the operation direction is forward.
Active when the operation direction is reverse.
Active when current is ≥ Pr.02-03.
Active when current is < Pr.02-03.
Reserved
Reserved
Activate when the power generation direction is verified.
Activate when the power generation direction runs forward.
Active when the actual output frequency is 0. The drive should be
in RUN mode.
Active when the actual output frequency is 0 or Stop. The drive
should be in RUN mode.
Active when Pr.02-71 is ON.
Active when Pr.02-72 is ON.
Active when Pr.02-73 is ON.
Active when Pr.02-74 is ON.
Reserved
Active when the output frequency reaches the frequency setting.
Reserved
8-01-11