Chapter 8 Descriptions of Parameter SettingsEB3000
02 Special Function Parameters
Starting Method
02-00
Serial Start Signal Selection
VF
Control Mode
Settings
 Selects the contactor serial start method.
 0: According to FWD/REV signal, the motor starts to run after the Enable signal MI = 40 is ON.
 1: According to Enable signal, the contactor, mechanical brake and DC brake all follow
parameters' setting to run after FWD/REV and Enable are ON.
SVC
FOCPG
0: According to FWD/REV signal
1: According to Enable drive function signal
Pr.02-00=0
Multi-function
0
output
1
MO= 15
No matter if the Enable Drive function signal outputs or not,
the drive starts to count Pr.03-02 after MO15 outputs.
: You can set this parameter during operation.
FOCPM
Enable Drive
0
False
True
8-02-2
Default: 0
1
False
True