Chapter 8 Descriptions of Parameter SettingsEB3000
02-21
Voltage of Emergency Power
VF
Control Mode
Settings
02-22
Power Capacity of Emergency Power (EPS)
VF
Control Mode
Settings
 When using emergency power (EPS), you must set the parameter to the required power
capacity for the emergency power, and then the AC motor drive calculates the acceptable
elevator speed (Pr.02-23) with the following equation.
I
= Pr.00-12 (Motor Rated Current)
motor_rated
√3 × I
V
eps_max =
f
V
eps_limit =
Pr.00-11
NOTE:
1. When the Frequency command > fEPS, the operation speed of emergency power (EPS) is fEPS.
2. When the Frequency command ≤ fEPS, the operation speed of emergency power (EPS) is set
according to the current Frequency command.
Auto-detection Timing Diagram 3
SVC
FOCPG
24.0–375.0 V
DC
48.0–750.0 V
DC
SVC
FOCPG
0.0–100.0 kVA
Pr.02-22 × 0.5
motor_rated
eps_max
× Pr.00-13
FOCPM
FOCPM
8-02-8
Default: 24.0 / 48.0
Default: 0.0