No.
RUN command is ON but STO circuit is not activated.
1
RUN command is ON and STO circuit is activated. Drive outputs immediately.
2
STO circuit is activated before RUN command is ON.
3
STO circuit is deactivated while the drive is outputting.
4
Time that the drive stops outputting.
5
Time that STO circuit is deactivated in normal condition.
6
RUN command is not ON when STO circuit is activated.
7
After Pr.04-14 detection time, if RUN command is still OFF or STO circuit is not deactivated, then STO
8
circuit sticking occurs.
04-11
Mechanical Brake Detection Time
VF
Control Mode
Settings
 When the mechanical brake function (Pr.01-00–Pr.01-07 are set to 42, 44) is not enabled within
this setting time, the drive displays fault code MbF (Mechanical brake feedback error).
04-12
Magnetic Contactor Detection Time
VF
Control Mode
Settings
 When the magnetic contactor function (Pr.01-00–Pr.01-07 are set to 41) is not enabled within
this setting time, the drive displays fault code MCF (Magnetic contactor error).
04-13
STO Timing Activation
VF
Control Mode
Settings
 Used with Pr.04-10=4–7.
STO Error Detection Timing Diagram
SVC
FOCPG
0.00–10.00 sec.
SVC
FOCPG
0.00–10.00 sec.
SVC
FOCPG
0: Triggers fault if an error occurs on timing activation
1: Triggers warning if an error occurs on timing activation (valid only when
using two-wire operation control)
Chapter 8 Descriptions of Parameter SettingsEB3000
Description
FOCPM
FOCPM
FOCPM
8-04-5
Default: 0.00
Default: 0.00
Default: 0