Chapter 8 Descriptions of Parameter SettingsEB3000
Settings
42
STO output status
43–44 Direct Docking Mode only
45
Reserved
Retrying after a fault has
46
occurred indication
47
Direct Docking Mode only
Control output of MPSCC (Motor
48
Phase Short Circuit Contactor)
49
Emergency power mode action
Analog Input / Output Settings
01-20
AUI1 Selection
01-26
AUI2 Selection
01-32
ACI Selection
Settings
0: No function
1: Frequency command
3: Load compensation
4–5: Reserved
6: P.T.C. thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
Functions
Contact Delta for more information
Reserved
Retry multiple outputs after an error has occurred. When the retry
period has finished, MO stops.
Contact Delta for more information
Active when the drive receives a RUN command.
Deactivated when the drive stops for more than Pr.03-05 time
(MPSCC Contracting Delay Time between Drive and Motor).
Active when the drive receives a power failure signal (Pr.01-00–
Pr.01-07 = 54) after Pr.02-28 (UPS Output Delay Time).
Deactivated when the drive receives a signal of disabling EPS
function (Pr.01-00–Pr.01-07 = 43) after Pr.02-29 (UPS Stops
Output Delay Time). For detailed information, see the EPS Flow
Chart in Pr.02-29.
Descriptions
Drive Status
Logic Output A
Either STO1 or
STO2 circuit is ON
STO active
Control Mode
8-01-12
STO Output Status
Logic Output B
(MO=42)
(MO=142)
OFF
ON
ON
OFF
Default: 1
Default: 0
Default: 0
VF
SVC
FOCPG FOCPM