Pr.00-23 Encoder Input Type Setting
 You must enter the correct pulse type for stable control.
 It is suggested that you set Pr.00-23 to 1 first. When fault code PGF1 occurs or the motor
does not run, set it to 2.
Pr.01-00–Pr.01-07 Multi-function Input Settings
 The default value of Pr.01-07 is 40 (Enable Drive). If you do not need this function (does not
work with controller), set the setting value to 0.
 Setting values:
0: No function
1: Multi-step speed command 1
2: Multi-step speed command 2
3: Multi-step speed command 3
4: Multi-step speed command 4
5: Reset
6: JOG command
7: Acceleration/deceleration speed inhibit
8: First, second acceleration/deceleration time
9: Third, fourth acceleration/deceleration time
10: EF input (Pr.02-16)
11: Reserved
12: Stop output
13–14: Reserved
15: AUI1 operation speed command
16: Reserved
17: AUI2 operation speed command
18: Emergency Stop (Pr.02-16)
19–23: Reserved
24: FWD JOG Command
25: REV JOG Command
6-9