Chapter 8 Descriptions of Parameter SettingsEB3000
01-08
Digital Input Response Time
VF
Control Mode
Settings
 Defines the digital input terminal signal delay and confirmation. The delay time prevents
interference that can cause errors (except for the counter input) in the digital terminal input
(FWD, REV and MI1–8). Increasing the setting for this parameter can reduce the errors, but it
delays the response time.
01-09
FWD/REV Terminal Contact Action
VF
Control Mode
Settings
 0: FWD/REV terminal is, by default, a N.O. contact (Normally Open).
 1: FWD terminal is set to N.C. (Normally Closed) contact.
 2: REV terminal is set to N.C. contact.
 3: FWD/REV terminal is set to N.C. contact.
Digital Output Settings
01-10
Multi-function Output 1: RA1, RB1, RC1 (Relay 1)
01-11
Multi-function Output 2: RA2, RC2 (Relay 2)
01-12
Multi-function Output 3: RA3, RC3 (Relay 3)
01-13
Multi-function Output 4: RA4, RC4 (Relay 4)
01-14
Multi-function Output 5: MO1
01-15
Multi-function Output 6: MO2
Settings
0: No function
1: Indication during operation
2: Operation speed reached
3: Desired frequency 1 reached (Pr.02-10, Pr.02-11)
4: Desired frequency 2 reached (Pr.02-12, Pr.02-13)
5: Zero Speed (Frequency command)
6: Zero speed with stop (Frequency command)
7: Over-torque (OT1) (Pr.04-40–04-42)
8: Reserved
9: Drive is ready
10: User-defined low-voltage detection (LV)
11: Fault indication
SVC
FOCPG
0.001–30.000 sec.
SVC
FOCPG
0: Disable
1: FWD terminal inversed
2: REV terminal inversed
3: FWD and REV terminals inversed
FOCPM
FOCPM
Control Mode
8-01-8
Default: 0.005
Default: 0
Default: 0
VF
SVC
FOCPG FOCPM