Delta EB3000 Series User Manual page 356

Elevator drive
Table of Contents

Advertisement

Abbreviated
ID No.
Fault Code
15
PHL
Action condition
Action time
Fault treatment parameter Pr.04-31 (Phase Loss Protection during Operation)
Reset method
Reset condition
Record
Cause
Phase loss of the input
power
Single-phase power input
on a three-phase model
The power voltage has
changed
Loose wiring terminal of
input power
Check if the input cable of
three-phase power is
broken
Unbalanced three-phase of
the input power
Brake discharge level is too
high
Abbreviated
ID No.
Fault Code
16
oH1
Action condition
Action time
Fault treatment parameter N/A
Reset method
Reset condition
Record
Cause
Check if the ambient temperature or
temperature inside the cabinet is
too high, or if there is obstruction in
the ventilation hole of the control
cabinet.
Check if there is any obstruction on
IGBT or if the fan is running
Insufficient ventilation space
Display on
Fault Name
KPED-LE02
Phase loss
Action and Reset
1: Software detection: DC bus is lower than Pr.07-51 (Brake Transistor Level) and DC
bus ripple is higher than 30V
2: Software detection: Power factor angle is smaller than 80 degree and DC bus ripple
is higher than 30V
3: Hardware automatically detects external phase loss
Hardware automatically detects external phase loss
Use Pr.04-02 to set to reset automatically or manually
Resets immediately when DC bus voltage is higher than Pr.07-51 (Brake Transistor
Level)
Pr.04-31 Phase Loss Protection during Operation (Default: 2)
When Pr.04-31=0, PHL is a warning and will not be recorded.
When Pr.04-31=1 or 2, PHL is a fault and will be recorded.
Verify wiring of the main circuit.
Use the model with voltage that matches the power.
If the power of main circuit works well, check if the MC of the main circuit is broken.
Cycle the power after verifying the power is normal. If PHL still occurs, return to the
factory for repair.
Tighten the terminal screws with the torque listed in the user manual.
Make sure the wiring is correct.
Replace the broken part of the cable.
Check the status of three-phase power.
Adjust Pr.07-51 (Brake Transistor Level) setting value.
Display on
Fault Name
KPED-LE02
IGBT overheating fault
Action and Reset
When IGBT temperature is higher than oH1 Fault Level shown in the table below
When IGBT temperature is higher than the protection level for more than 100 ms
Manual reset
Resets manually when temperature is lower than [IGBT limits – 5°C]
Yes
1. Check the ambient temperature.
2. Regularly inspect the ventilation hole of the control cabinet.
3. Change the installed place if there are heating objects, such as brake
resistors, in the surroundings.
4. Install/add cooling fan or air conditioner to lower the temperature inside the
cabinet.
Remove the obstruction or replace the cooling fan.
Increase ventilation space of the drive.
Chapter 9 Warning and Fault CodesEB3000
Input phase loss warning
Corrective Actions
If IGBT temperature is higher than oH1 Fault
Level shown in the table below when drive
detects overheating of IGBT, keypad displays
oH1 fault, not oH1 warning.
Corrective Actions
9-25
Description
Description
<Go to
List of Fault
Codes>