Delta EB3000 Series User Manual page 234

Elevator drive
Table of Contents

Advertisement

Mains power outage
Magnetic Contactor
MI=54
Check if
power is off
Pr.02-28
Delay time (sec.)
MO=49
is ON
The steps to set battery as EPS are as follows:
1.
Set MI = 54 (Power failure signal)
2.
Set MI = 43 (EPS function)
3.
Set MO = 49 (Emergency power mode action)
4.
Set Pr.02-20 = EPS mode selection
5.
Set Pr.02-21 = Emergency power voltage running
6.
Set Pr.02-22 = Emergency power capacity running
7.
Set Pr.02-24 = Power generation direction search time
8.
Set Pr.02-25 = Detecting level of power factor at the direction of power generation
9.
Set Pr.02-28 = MO enables UPS delay time
10. Set Pr.02-29 = MO disables UPS delay time
NOTE: When using battery as EPS in an elevator system, auxiliary contact of the contactor should be used to
judge whether to cut off the power and notify the drive.
UPS is ON
The host sends [EPS
Enable] to [MI=43
NO
MI=43
Check
Enable
YES
Sends FWD/REV
commands
The elevator
reaches the level
Disables FWD/REV
commands
EPS Flow Chart (Battery)
8-02-11
Chapter 8 Descriptions of Parameter SettingsEB3000
NO
The host sends [EPS
Disable] to [MI=43
MI=43
Check
Disable
Pr.02-29
Delay time (sec.)
MO=49
is OFF
UPS is OFF