Chapter 8 Descriptions of Parameter SettingsEB3000
Bit 3
Bit 2
1
1
-
1
1
1
-
02-71
Fault Output Option 1
02-72
Fault Output Option 2
02-73
Fault Output Option 3
02-74
Fault Output Option 4
VF
Control Mode
Settings
 You can use these parameters with multi-function output (set Pr.01-10–Pr.01-15 to 35–38) for
the specific requirement. When a fault occurs, the corresponding terminals are activated. You
must convert binary value to decimal value when setting Pr.02-71–Pr.02-74.
Fault Code
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed (ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low voltage during acceleration (LvA)
12: Low voltage during deceleration (Lvd)
13: Low voltage during constant speed (Lvn)
14: Low voltage at stop (LvS)
15: Phase loss (PHL)
16: IGBT overheating fault (oH1)
18: IGBT temperature detection failure (tH1o)
21: Overload (oL)
Bit 1
Bit 0
1
0
1
1
0
1
-
-
-
1
1
0
1
1
0
1
1
0
-
-
-
SVC
FOCPG
0–65535 sec. (refer to bit table for fault code)
93: CANLift disconnection (CndL)
95: CANLift error (CnLF)
96: STO disconnection (Stod)
97: STO at running (Stor)
98: STO circuit sticking fault (StoS)
99: Ignore STO is ON (iSto)
100: Over ripple protection (orP)
FOCPM
Bit0
Bit1
Bit2
current
Volt.
OL
8-02-20
Fault Code
Default: 0
Bit3
Bit4
Bit5
SYS
FBK
EXI
Bit6
CE