Chapter 8 Descriptions of Parameter SettingsEB3000
03 Comfort Adjustment Parameters
Delay Time
03-00
Brake Release Delay Time when Elevator Starts
VF
Control Mode
Settings
03-01
Brake Engage Delay Time when Elevator Stops
VF
Control Mode
Settings
When the AC motor drive runs and after the delay time in Pr.03-00, the corresponding multi-
function output terminal (12: mechanical brake release) is ON.
When the AC motor drive stops and after the delay time in Pr.03-01, the corresponding multi-
function output terminal (12: mechanical brake release) is OFF.
Use this function with the DC brake function.
03-02
Magnetic Contactor Contracting Delay Time between Drive and Motor
03-03
Magnetic Contactor Release Delay Time between Drive and Motor
VF
Control Mode
Settings
After running, use these parameters with multifunction input terminal setting 40 (Enable drive
function), and multifunction output terminal setting 15 (motor-controlled magnetic contactor
output). When the multifunction output terminals are ON, the drive starts outputting after the
delay time in Pr.03-02. When the drive stops outputting, multifunction output terminals release
after the delay time in Pr.03-03.
SVC
FOCPG
0.000–65.000 sec.
SVC
FOCPG
0.000–65.000 sec.
SVC
FOCPG
0.010–65.000 sec.
: You can set this parameter during operation.
FOCPM
FOCPM
FOCPM
8-03-2
Default: 0.250
Default: 0.250
Default: 0.200