Chapter 8 Descriptions of Parameter SettingsEB3000
01-24
AUI1 Input Filter Time
01-30
AUI2 Input Filter Time
01-36
ACI Input Filter Time
VF
Control Mode
Settings
Analog signals, such as those entering AUI1, AUI2 and ACI, are commonly affected by
interference that affects the stability of the analog control. Use the Input Noise Filter to create a
more stable system.
If Pr.01-24 is large, the control is more stable, but the response to the input is slower. If Pr.01-
24 is small, the control may be unstable, but the response to the input is faster.
01-25
AUI1 Input Type
01-31
AUI2 Input Type
VF
Control Mode
Settings
When this parameter is set to 0 (bipolar), the input function direction is determined by the input
signal.
0: And Pr.01-20=1, AUI decides the operation direction.
1: And Pr.01-20=1, the FWD/REV terminal decides the operation direction.
AUI1: Use Switch (SW4) set as ACI or AVI.
AUI2: only AVI is available.
01-40
Analog Output Selection 1
01-43
Analog Output Selection 2
VF
Control Mode
Settings
SVC
FOCPG
0.00–2.00 sec.
SVC
FOCPG
0: Bipolar (±10 V)
1: Unipolar (0–10 V)
SVC
FOCPG
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (RPM)
3: Output current (rms)
4: Output voltage
5: DC bus voltage
6: Power factor angle
7: Power factor
8: Output torque
9: AUI1
10: Reserved
11: AUI2
12: q-axis current
13: q-axis feedback value
14: d-axis current
15: d-axis feedback value
8-01-16
FOCPM
Default: 0.01
FOCPM
Default: 0
FOCPM
Default: 0