Chapter 9 Warning and Fault CodesEB3000
Abbreviated
ID No.
Fault Code
7
ovA
Action condition
Action time
Fault treatment parameter Stops output immediately, and coasts to stop.
Reset method
Reset condition
Record
Cause
Acceleration time is too
short
Power voltage changes
Malfunction caused by
interference
Abbreviated
ID No.
Fault Code
8
ovd
Action condition
Action time
Fault treatment parameter Stops output immediately, and coasts to stop.
Reset method
Reset condition
Record
Cause
Deceleration time is too
short
Power voltage changes
Malfunction caused by
interference
Abbreviated
ID No.
Fault Code
9
ovn
Action condition
Action time
Fault treatment parameter Stops output immediately, and coasts to stop.
Reset method
Reset condition
Record
Cause
Power voltage changes
Malfunction caused by
interference
Display on
Fault Name
KPED-LE02
Over-voltage during
acceleration
Action and Reset
DC bus is higher than 410V / 820V
Immediately act
Use Pr.04-02 to set to reset automatically or manually
Resets when DC bus is lower than 369V / 738V
Yes
If the DC bus over-voltage occurs due to the regenerative voltage of motor inertia,
increase the acceleration time.
Check if the input voltage is within the rated drive input voltage range, and check for
possible voltage spikes.
Verify the wiring of the control circuit and the wiring/grounding of the main circuit to
prevent interference.
Display on
Fault Name
KPED-LE02
Over-voltage during
deceleration
Action and Reset
DC bus is higher than 410V / 820V
Immediately act
Use Pr.04-02 to set to reset automatically or manually
Resets when DC bus is lower than 369V / 738V
Yes
If the DC bus over-voltage occurs due to the regenerative voltage of motor inertia,
increase the deceleration time.
Check if the input voltage is within the rated drive input voltage range, and check for
possible voltage spikes.
Verify the wiring of the control circuit and the wiring/grounding of the main circuit to
prevent interference.
Display on
Fault Name
KPED-LE02
Over-voltage during
constant speed
Action and Reset
DC bus is higher than 410V / 820V
Immediately act
Use Pr.04-02 to set to reset automatically or manually
Resets when DC bus is lower than 369V / 738V
Yes
Check if the input voltage is within the rated drive input voltage range, and check for
possible voltage spikes.
Verify the wiring of the control circuit and the wiring/grounding of the main circuit to
prevent interference.
DC bus over-voltage during acceleration
Corrective Actions
DC bus over-voltage during deceleration
Corrective Actions
DC bus over-voltage during constant speed
Corrective Actions
9-22
Description
Description
Description
<Go to
List of Fault
Codes>

Advertisement

Table of Contents
loading

Table of Contents