Chapter 8 Descriptions of Parameter SettingsEB3000
00-02
Master Frequency Command Source
VF
Control Mode
Settings
 Determines the drive's master frequency source.
00-03
Operation Command Source
VF
Control Mode
Settings
 The EB3000 series motor drives are shipped without a digital keypad, but you can use the
external terminals or RS-485 to control the operation command.
00-04
Output Direction Selection
VF
Control Mode
Settings
 Use this parameter when elevator running direction is opposite to the command direction.
Motor Parameters
00-10
Motor Rated Power
VF
Control Mode
Settings
 Sets the rated power of the motor. The default is the power of the drive.
00-11
Motor Rated Voltage
VF
Control Mode
Settings
 Set this parameter according to the rated voltage on the motor nameplate. If the motor is 220V,
set this parameter to 220.0. If the motor is 200V, set this parameter to 200.0.
 There are many motor types in the market and the power system for each country is also
different. The economical and convenient solution is to install an AC motor drive. Then there is
no problem using the motor with different voltage and frequency inputs, and the motor drive can
improve the original motor characteristics and useful life.
SVC
FOCPG
1: RS-485 serial communication or keyboard panel (KPED-LE02)
2: External analog input (Pr.01-20)
3: External digital input
4: Direct docking mode (Delta CAN). Contact Delta for more information.
5: Direct docking mode (Delta CAN + Terminal (FWD/REV)). Contact Delta
for more information.
6: CAN Lift. Contact Delta for more information.
SVC
FOCPG
1: External terminals
2: RS-485 serial communication or digital keypad (KPC-CC01)
3: Keyboard panel (KPED-LE02)
6: CAN Lift. Contact Delta for more information.
SVC
FOCPG
0: FWD: counterclockwise, REV: clockwise
1: FWD: clockwise, REV: counterclockwise
SVC
FOCPG
0.00–655.35 kW
SVC
FOCPG
230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
8-00-8
FOCPM
Default: 1
FOCPM
Default: 1
FOCPM
Default: 0
FOCPM
Default: #.##
FOCPM
Default: 220.0 / 440.0