00-12
Motor Rated Current
VF
Control Mode
Settings
Set this value according to the rated motor current from the motor nameplate.
Example: Suppose the rated current for 7.5 HP (5.5 kW) models is 25 A and the default is 22.5 A.
In this way, the current range is from 10 A (25 × 40%) to 30 A (25 × 120%).
As shown in the table below, the defaults vary according to the different motor drive outputs in
HP and in kW.
Motor Drive's Output (HP)
Motor Drive's Output (kW)
Motor Rated Current (A)
230V Models
Motor Rated Current (A)
460V Models
00-13
Motor Rated Frequency
VF
Control Mode
Settings
Sets this value according to the motor nameplate. In general, set this value equal to motors
rated frequency.
Sets the drive's maximum operating frequency range. The formula is: Pr.00-13 = (Pr.00-15
Number of Motor Poles × RPM when elevator runs with rated speed) ÷ 120
00-14
Motor Rated Speed
VF
Control Mode
Settings
Sets this value according to the motor nameplate.
Speed (RPM) = (120 × Frequency) ÷ Number of Motor Poles
00-15
Number of Motor Poles
VF
Control Mode
Settings
Sets this value according to the motor nameplate.
Sets the number of motor poles (must be an even number).
00-16
IM Motor No-load Current
Control Mode
Settings
As shown in the table below, the defaults vary according to the different motor drive output in
HP and in kW.
SVC
FOCPG
[(40–120%) × Pr.07-01] Amps
2.2
9.82 13.91 16.36 19.64 24.54 36.82 47.46
Default
Default
SVC
FOCPG
0.00–400.00 Hz
SVC
FOCPG
0–65535 rpm
SVC
FOCPG
2–96
SVC
FOCPG
0–Pr.00-12 Amps
Chapter 8 Descriptions of Parameter SettingsEB3000
FOCPM
3*
5*
5
7.5
3.7
4
5.5
9.41
10.64 13.91 18.82 24.54
FOCPM
FOCPM
FOCPM
8-00-9
Default: #.##
10
15
20
7.5
11
15
*: Single-phase models.
Default: 60.00 / 50.00
Default: 1710
Default: 4
Default: #.##
25
18.5
63
31.1