Chapter 8 Descriptions of Parameter SettingsEB3000
09 Communication Parameters
Modbus
When using the communication interface, the diagram on the
right shows the communication port pin definitions. It is
recommended that you connect the AC motor drive to your
PC by using Delta IFD6530 or IFD6500 as a communication
converter. For details on Modbus communication protocol,
see Appendix B. Modbus Protocol.
09-00
Communication Address
VF
Control Mode
Settings
 Sets the communication address for the drive if the AC motor drive is controlled through RS-485
serial communication. The communication address for each AC motor drive must be unique.
09-01
Transmission Speed
VF
Control Mode
Settings
 Sets the transmission speed between the RS-485 master (PLC, PC, etc.) and the AC motor
drive.
09-02
Communication Protocol
VF
Control Mode
Settings
SVC
FOCPG
1–254
SVC
FOCPG
4.8–115.2 kbps
SVC
FOCPG
0: 7, N, 1 for ASCII
1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII
9: 8, O, 1 for ASCII
10: 8, E, 2 for ASCII
11: 8, O, 2 for ASCII
12: 8, N, 1 for RTU
13: 8, N, 2 for RTU
14: 8, E, 1 for RTU
15: 8, O, 1 for RTU
16: 8, E, 2 for RTU
17: 8, O, 2 for RTU
: You can set this parameter during operation.
FOCPM
FOCPM
FOCPM
8-09-2
Default: 1
Default: 19.2
Default: 13