00-79
JOG Acceleration Time
00-80
JOG Deceleration Time
VF
Control Mode
Settings
 You can use the external terminal JOG. When the JOG command is ON, the AC motor drive
accelerates from the fourth output voltage setting (Pr.03-55) to the JOG frequency (Pr.00-66).
When the JOG command is OFF, the AC motor drive decelerates from the JOG frequency to
zero. The Acceleration and Deceleration time are set by these parameters (Pr.00-79, Pr.00-80).
 You cannot execute the JOG command when the AC motor drive is running. When the JOG
command is running, other operation commands are invalid except the Forward and Reverse
commands.
SVC
FOCPG
0.00–600.00 sec.
8-00-21
Chapter 8 Descriptions of Parameter SettingsEB3000
FOCPM
Default: 1.00