Chapter 7 Summary of Parameter SettingsEB3000
Pr.
Parameter Name
 04-21
Slip Deviation Level
Slip Deviation Detection
 04-22
Time
 04-30
Low Voltage Level
Phase Loss Protection
 04-31
during Operation
Phase Loss Detection of
04-32
Drive Output at Start-up
(MPHL)
04-33
MPHL Speed Level
04-34
MPHL Current Level
04-35
MPHL Count Time
04-37
Over Ripple Protection
Over-torque Detection
 04-40
(OT1)
Over-torque Detection
 04-41
Level (OT1)
Over-torque Detection
 04-42
Time (OT1)
PTC (Positive
 04-50
Temperature Coefficient)
Detection Action
 04-51
PTC Level
PTC Detection Filter
 04-52
Time
04-53
Electronic Thermal Relay
Setting Range
2: Warn and coast to stop
0.0–100.0%
0: Disable
0.0–10.0 sec.
230V models: 160.0–220.0 V
460V models: 320.0–440.0 V
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and coast to stop
0: Disable
1: Enable
0.00–15.00 Hz
0.00–10.00% (of rated current)
10.0–1000.0
0: Disable
1: Enable
0: Over-torque detection disabled
1: Over-torque detection during
constant speed operation, continue to
operate after detection
2: Over-torque detection during
constant speed operation, stop
operating after detection
3: Over-torque detection during
operation, continue to operate after
detection
4: Over-torque detection during
operation, stop operating after
detection
10–250% (rated current of the motor
drive)
0.1–60.0 sec.
0: Warn and keep operation
1: Fault and ramp to stop
0.0–100.0%
0.00–10.00 sec.
0: Standard motor (motor with fan on
the shaft)
1: Inverter motor (with external forced
cooling)
2: Disabled
7-18
Default
0.0
1.0
180.0 /
360.0
2
0
10.00
5.50
30.0
1
0
150
0.1
0
50.0
0.20
2