Chapter 9 Warning and Fault CodesEB3000
Abbreviated
ID No.
Fault Code
40
AUE
Action condition
Action time
Fault treatment parameter N/A
Reset method
Reset condition
Record
Cause
Press STOP key during
auto-tuning
Incorrect motor capacity
(too large or too small) and
parameter setting
Incorrect motor wiring
Motor shaft lock
The magnetic contactor
installed at the drive output
(U/V/W) is Open
The load is too large.
Incorrect encoder signal
(PGHH)
Abbreviated
ID No.
Fault Code
42
PGF1
Action condition
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Incorrect parameter setting
of encoders
Check if A/B wiring of the
encoder is reverse
Display on
Fault Name
KPED-LE02
Auto-tuning error
Action and Reset
1. When detecting stator resistance, output current is smaller than 5% of the drive's
rated current and time exceeds 0.5 sec.
2. Incorrect encoder signal for PGHH during auto-tuning.
0.5 sec.
Manual reset
Resets immediately
Yes
Re-execute auto-tuning.
Verify motor specification and set motor parameter settings again (Pr.00-10–Pr.00-16).
Check the wiring.
Remove the cause of motor shaft lock.
Make sure the magnetic contactor is Closed.
Reduce the load.
Replace the motor with a larger capacity model.
1. Check if the A/B/C/D wiring is correct.
2. Check if the signal line of the encoder is interfered.
Display on
Fault Name
KPED-LE02
Opposite PG feedback
direction
Action and Reset
1. Encoder input type does not set (Pr.00-23 = 0)
2. Feedback direction is opposite to the frequency command direction
Pr.04-71 Encoder Feedback Signal Fault Detection Time (Default: 1.0 second)
Pr.04-70 (Default: 2)
0: Warn and keep operation
1: Fault and ramp to stop
2: Fault and stop operation
Auto
When Pr.04-70=0, PGF1 is a warning and will be automatically cleared.
Manual When Pr.04-70=1 or 2, PGF1 is a fault and must be reset manually.
Resets immediately
If PGF1 is a warning, it will not be recorded.
If PGF1 is a fault, it will be recorded.
Set encoder parameter settings again (Pr.00-23)
Ensure the A/B wiring is correct.
Motor auto-tuning error
Corrective Actions
The motor runs in a reverse direction to the
frequency command direction, and the time
error occurred exceeds Pr.04-71 detection
time.
Corrective Actions
9-32