Delta EB3000 Series User Manual page 215

Elevator drive
Table of Contents

Advertisement

Chapter 8 Descriptions of Parameter SettingsEB3000
Settings
0
No function
1
Indication during operation
2
Operation speed reached
Desired frequency 1 reached
3
(Pr.02-10)
Desired frequency 2 reached
4
(Pr.02-12)
Zero Speed
5
(Frequency command)
Zero Speed with stop (Frequency
6
command)
Over-torque (OT1)
7
(Pr.04-40–Pr.04-42)
8
Reserved
9
Drive is ready
User-defined low-voltage
10
detection
11
Fault indication
Mechanical brake release (Pr.03-
00, Pr.03-01, Pr.02-02)
12
13
IGBT overheat warning (oH1)
14
Brake transistor signal
Motor-controlled magnetic
15
contactor output
Functions
MO has no function
Active when there is an output from the drive or RUN command is
ON.
Active when the AC motor drive reaches the output frequency
setting.
Active when the desired frequency (Pr.02-10) reached.
Active when the desired frequency (Pr.02-12) reached.
Active when the Frequency command = 0. (the drive should be at
RUN mode)
Active when Frequency command = 0 or Stop.
Active when detecting over-torque. Refer to Pr.04-40 (over-torque
detection-OT1), Pr.04-41 (over-torque detection level-OT1) and
Pr.04-42 (over-torque detection time-OT1).
Reserved
Active when the drive is ON and no error detected.
Active when the DC bus voltage is too low (see Pr.04-30 Low
voltage level).
Active when a fault occurs (except Lv stop).
When the drive runs according to Pr.03-00, it is ON. Use this
function with the DC brake. It is recommended to use contact "b"
(N.C).
Active when IGBT overheats. To prevent oH, turn off the drive
(refer to Pr.04-55).
Activated when the drive needs help braking the load. This
function helps achieve a smooth deceleration (refer to Pr.07-51).
Active when you set MI function to #40 (Enable drive function).
Descriptions
8-01-10