Delta EB3000 Series User Manual page 63

Elevator drive
Table of Contents

Advertisement

Chapter 4 WiringEB3000
4-4 Main Circuit Terminal Specifications
Frame A
Applicable models:
VFD022ED21B, VFD022ED21BE, VFD037ED21B, VFD037ED21BE
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
Model
Stripping
Length
(mm)
VFD022ED21B
VFD022ED21BE
12–13
VFD037ED21B
VFD037ED21BE
NOTE:
 When wiring bare wires, ensure that they are perfectly arranged to go through the wiring holes.
 If you install at Ta 45°C environment, use copper wires with voltage rating of 600V and
temperature resistance of 75°C or 90°C.
 If you install at Ta 45°C above environment, use copper wires with voltage rating of 600V and
temperature resistance of 90°C or above.
 To be UL installation compliant, you must use copper wires when installing. The wire gauge is
based on temperature resistance of 75°C, in accordance with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
 Use a flathead screwdriver to tighten the wires. The head width and thickness of the flathead
screwdriver are 5.5 mm and 1.0 mm.
Figure 4-10
Main Circuit Terminals
DC-, DC+/+1, +2/B1, B2
Max.
Min.
Wire
Wire
Gauge
Gauge
10 mm
2
16 mm
(8 AWG)
2
(6 AWG)
16 mm
2
(6 AWG)
Stripping
Torque
Length
(±10%)
(mm)
20.74 kg-cm
(18.0 lb-in.)
12–13
(2.03 Nm)
4-10
Terminals
Max.
Min.
Torque
Wire
Wire
(±10%)
Gauge
Gauge
10 mm
2
10 mm
2
20.74 kg-cm
(8 AWG)
(8 AWG)
(18.0 lb-in.)
16 mm
2
16 mm
2
(2.03 Nm)
(6 AWG)
(6 AWG)
Table 4-2

Advertisement

Table of Contents
loading

Table of Contents