Chapter 8 Descriptions of Parameter SettingsEB3000
04-14
STO Sticking Detection Time
VF
Control Mode
Settings
 When FWD/REV command is OFF and STO circuit is continuously ON for more than Pr.04-14
detection time, STO circuit sticking is malfunctioned.
 Pr.04-10=5: Stoc warning occurs. This warning will be automatically cleared when FWD/REV
command is ON or STO circuit is OFF.
 Pr.04-10=6: StoS fault occurs. This fault can be cleared by pressing RESET key manually.
 Pr.04-10=7: StL4 fault occurs. This fault cannot be cleared and must be powered-on again.
Slip Compensation Level
04-20
Over-slip Action
Control Mode
Settings
04-21
Slip Deviation Level
Control Mode
Settings
04-22
Slip Deviation Detection Time
Control Mode
Settings
 Pr.04-20–Pr.04-22 set the allowable slip level and over-slip action when the drive is running.
Phase Loss Protection
04-30
Low Voltage Level
VF
Control Mode
Settings
 Sets the Lv level.
SVC
FOCPG
0.0–10.0 sec.
SVC
FOCPG
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
SVC
FOCPG
0.0–100.0%
0: Disable
SVC
FOCPG
0.0–10.0 sec.
SVC
FOCPG
230V models: 160.0–220.0 V
460V models: 320.0–440.0 V
FOCPM
FOCPM
8-04-6
Default: 2.0
Default: 0
Default: 0.0
Default: 1.0
Default: 180.0 / 360.0