Chapter 8 Descriptions of Parameter SettingsEB3000
V/F Curve
03-50
Maximum Output Frequency
VF
Control Mode
Settings
Determines the AC motor drive's Maximum Output Frequency. All the AC motor drive frequency
command sources (analog inputs -10–10 V) are scaled to correspond to the output frequency
range.
03-51
Second Output Frequency Setting
VF
Control Mode
Settings
03-52
Second Output Voltage Setting
VF
Control Mode
Settings
03-53
Third Output Frequency Setting
VF
Control Mode
Settings
03-54
Third Output Voltage Setting
VF
Control Mode
Settings
03-55
Fourth Output Frequency Setting
VF
Control Mode
Settings
03-56
Fourth Output Voltage Setting
VF
Control Mode
Settings
You usually set the V/F curve according to the motor's allowable loading characteristics. Pay
special attention to the motor's heat dissipation, dynamic balance, and bearing lubrication when
the loading characteristics exceed the loading limit of the motor.
The frequency setting of V/F curve must be set according to this rule: Pr.00-13 ≥ Pr.03-51 ≥
Pr.03-53 ≥ Pr.03-55. There is no limit for the voltage setting, but a high voltage at low frequency
may cause motor burnout, overheating, and trigger stall prevention or over-current protection.
Use low voltages at low frequencies to prevent motor damage or drive malfunction.
SVC
FOCPG
5.00–400.00 Hz
0.00–400.00 Hz
230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
0.00–400.00 Hz
230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
SVC
FOCPG
0.00–400.00 Hz
SVC
230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
FOCPM
8-03-8
Default: 60.00 / 50.00
Default: 0.50
Default: 5.0 / 10.0
Default: 0.50
Default: 5.0 / 10.0
Default: 0.00
Default: 5.0 / 10.0