Chapter 8 Descriptions of Parameter SettingsEB3000
See Pr.08-67, Pr.08-71, Pr.08-75, Pr.08-79, Pr.08-83, Pr.08-87, Pr.08-91, and Pr.08-95 (mode
selections of trigger unit 1 to 8).
08-67
Mode Selection of Trigger Unit 1
08-71
Mode Selection of Trigger Unit 2
08-75
Mode Selection of Trigger Unit 3
08-79
Mode Selection of Trigger Unit 4
08-83
Mode Selection of Trigger Unit 5
08-87
Mode Selection of Trigger Unit 6
08-91
Mode Selection of Trigger Unit 7
08-95
Mode Selection of Trigger Unit 8
VF
Control Mode
Settings
Once parameters regarding trigger are changed, the internal status of all units will be reset. One
second after parameters regarding trigger are changed, all units start to operate.
Among all 8 trigger units, only one configuration is allowed to be set to 3 (Timing trigger mode)
at one time.
Comparator trigger mode
Config1(Source)
Config2(Threshold)
Config3:
0: A>B
, B is threshold
1: A<B
, B is threshold
2: A==B
, B is threshold
3: A!=B
, B is threshold
4: A>B
, Both A and B are Source
5: A<B
, Both A and B are Source
6: A==B
, Both A and B are Source
7: A!=B
, Both A and B are Source
8: (A==0) && (B==0) , Both A and B are Source
9: (A!=0) && (B!=0) , Both A and B are Source
10: (A==0) || (B==0) , Both A and B are Source
11: (A!=0) || (B!=0) , Both A and B are Source
SVC
FOCPG
0: None
1: Comparator trigger mode
2: Fault code trigger mode
3: Timing trigger mode
4: Differential trigger mode
5: Value repeat captured trigger mode
6: External (MI) trigger mode
7: Reserved
Mode 1
A
C
B
Config3
FOCPM
Fault code trigger mode
Config1
A
Config2
B
C
Config3
NOTE: For details on fault code, see Chapter 9
Fault Codes and Descriptions.
8-08-6
Default: 0
Mode 2
(Error == Config1) ||
D
(Error == Config2) ||
(Error == Config3)