Delta EB3000 Series User Manual page 218

Elevator drive
Table of Contents

Advertisement

 When using the Frequency command, the corresponding value for 0 to ±10 V or 4–20 mA is 0–
maximum output frequency (Pr.03-50). When the Frequency command of analog input is
transferred from positive voltage to negative voltage or negative voltage to positive voltage, a
RUN command should be given again to ensure an opposite direction is run.
 When using load compensation, the corresponding value for 0 to ±10 V or 4–20 mA is 0–moto's
rated torque.
01-21
AUI1 Input Bias
VF
Control Mode
Settings
 Sets the corresponding AUI1 voltage for the external analog input 0.
SVC
FOCPG
-100.0–100.0%
8-01-13
Chapter 8 Descriptions of Parameter SettingsEB3000
FOCPM
Default: 0.0

Advertisement

Table of Contents
loading

Table of Contents