Nortel DMS-10 Series Installation, Operation And Maintenance Manual page 96

Billing media converter ii
Hide thumbs Also See for DMS-10 Series:
Table of Contents

Advertisement

2-68 Section 060-INDP-111 System Description
CURRENT ALARM ASSIGNMENTS ARE:
DEV/EVT # NAME
* 01 NO BLK LAST PER MINOR
02 TEC STNBY FAIL MINOR
03 TEC PRIME FAIL MAJOR
* 04 D-RAM ERROR
.
.
33 DISK ER MESSAGE MINOR
* INDICATES CURRENTLY ACTIVE ALARM(S)
TO CHANGE ERRMAP TABLE, ENTER:
ERRMAP DEV/EVT# ALARMTYPE LEVEL
EXAMPLE: ERRMAP 2 MINOR 1
Enter the following at the maintenance terminal to assign or change an alarm
event, alarm type, or alarm level:
>ERRMAP event alarmtype level (cr)
where: event
If a Level 0 alarm occurs, no Processor switch takes place. Levels 1-3
establish the priorities of the remaining alarms. If an alarm occurs that is a
higher level alarm than the highest Level active alarm on the standby side, a
Processor switch takes place.
Enter the following at the maintenance terminal to INHIBIT a selected alarm:
>ERRMAP event# INHIBIT level (cr)
297-6201-502 Standard 01.02 September 2000
ALARM LEVEL
MAJOR
Note: To clear an active alarm after the condition is no longer pre-sent,
enter RSERR 00 to reset all alarms, or DEVICE/EVENT#. (1 or 2 digits)
to clear a specific alarm. For more information, refer to the information
regarding the RSERR command in the Command and Message Guide
section.
CAUTION
Use of this command may cause loss of data. Consult
with technical assistance personnel before changing
alarm level assignments.
- Device/Event Number (0-99)
alarmtype - INHIBIT, MINOR, MAJOR, or CRITICAL.
level
- Severity Level (0-3)
0 - No Switch (Processor)
1 - Least Serious
2
3 - Most Serious.
1
0
1
1
0