Nortel DMS-10 Series Installation, Operation And Maintenance Manual page 342

Billing media converter ii
Hide thumbs Also See for DMS-10 Series:
Table of Contents

Advertisement

4-182 Section 060-INDP-410 Command and Message Guide
Table 7-112
DPR TEST FAILED message
2 2 9
(log message)
DPR TEST FAILED
ADR:xxxx RD:yy WR:zz
Display: Maintenance terminal
2 3 0
Alarm Level:
Processor switch
2 3 1
Customer-Selected Alarm Level
2 3 2
Other Alarm Indications
2 3 3
System Recovery Action
2 3 4
Craftsperson Activity:
297-6201-502 Standard 01.02 September 2000
Where:
xxxx = DPR address where the fault occurred (in Hex).
yy = incorrect value read from memory (in Hex).
zz = expected value that was written to memory (in
Hex).
Cause: output when the DPR test, initiated by the TEST
command, or the DPRTST command, and executed on
the standby processor, does not obtain the expected
results
Reason Code = 21
Corresponds to ERRMAP entry: DSK CRD HW ERR
System Default:
Type:MajorLevel:2
Type:Level:
Default:
Status Panel:MajorAudible:Major
Customer-Selected
Status Panel:Audible:
None
Replace the SCSI Interface PCA using the
Miscellaneous PCA Replacement Procedure for the in
the Maintenance Procedures Guide section.