Nortel DMS-10 Series Installation, Operation And Maintenance Manual page 595

Billing media converter ii
Hide thumbs Also See for DMS-10 Series:
Table of Contents

Advertisement

Procedure 6-38
Error Control II Jumper PCA replacement (NTM609AB)
Step
Description
96
To clear any alarms on the active processor, enter at the maintenance terminal:
>RSERR 00 (cr)
Alarms will clear if there are no faults.
97
When all maintenance activities are complete, be sure to replace the front panel of the
BMC. Carefully line up the four captive screws of the front panel with their mounting
holes. Tighten the captive screws; but do not bear down.
The procedure is complete.
BMC II BISYNC Operation, Administration, and Maintenance Guide BMCB001 and up
Section 060-INDP-610 Maintenance Procedures Guide 6-157
(Sheet 3 of 3)