Second Function Selection Signal (Rt Signal); Inverter Output Shutoff Signal (Mrs Signal, Pr. 17) - Mitsubishi Electric 700 Series Instruction Manual

Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

5.11.3

Second function selection signal (RT signal)

When the RT signal turns ON, the second function becomes valid.
The second function has the following applications.
(a) Switching between normal use and emergency use
(b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line
acceleration/deceleration
(d) Switching of characteristic between the main motor and sub
motor
When the RT signal is ON, the following second functions are selected at the same time.
Function
Torque boost
Base frequency
Acceleration time
Deceleration time
Electronic thermal O/L relay
Stall prevention
Applied motor

5.11.4 Inverter output shutoff signal (MRS signal, Pr. 17)

The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected.
Parameter
Name
Number
17
MRS input selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
The motor coasts to stop
ON
MRS Signal
STF (STR)
ON
signal
First Function
Second Function
Parameter Number
Parameter Number
Pr. 0
Pr. 3
Pr. 7
Pr. 8
Pr. 9
Pr. 22
Pr. 71
Initial Value
0
(1)
Output shutoff signal (MRS signal)
Turning ON the output shutoff signal (MRS) during inverter running
shuts off the output immediately.
MRS signal may be used as described below.
(a) When mechanical brake (e.g. electromagnetic brake) is used to stop
motor
The inverter output is shut off when the mechanical brake operates.
Time
(b) To provide interlock to disable operation by the inverter
With the MRS signal ON, the inverter cannot be operated if the start
signal is entered into the inverter.
(c) Coast the motor to a stop.
When the start signal is turned OFF, the inverter decelerates the
motor to a stop in the preset deceleration time, but when the MRS
signal is turned ON, the motor coasts to a stop.
(2)
MRS signal logic inversion (Pr. 17)
When Pr. 17 is set to "2", the MRS signal (output stop) can be changed
to the normally closed (NC contact) input specification. When the MRS
signal turns ON (opens), the inverter shuts off the output.
Second acceleration/deceleration time
RT
RH
RM
Refer to
Page
Pr. 46
94
Pr. 47
107
Pr. 44
116
Pr. 44, Pr. 45
116
Pr. 51
123
Pr. 48
101
Pr. 450
125
Setting Range
0, 4
2
I/O signal control
Acceleration time
is reflected
Time
Description
Normally open input
Normally closed input
(NC contact input specifications)
5
143

Hide quick links:

Advertisement

Table of Contents
loading