Inverter Output Shutoff Signal (Mrs Signal, Pr. 17) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Parameter
6.10.2

Inverter output shutoff signal (MRS signal, Pr. 17)

The inverter output can be shut off from the MRS signal. The logic of the MRS signal can also be se-
lected.
Pr. No. Name
17
MRS input selection
The above parameter can be set when Pr. 160 "User group read selection" = 0.
Output shutoff signal
Turning on the output shutoff signal (MRS) during inverter running shuts off the output immediately.
MRS
STF (STR)
Terminal MRS may be used as described below:
● When mechanical brake (e.g. electromagnetic brake) is used to stop motor.
The inverter output is shut off when the mechanical brake operates.
● To provide interlock to disable operation by the inverter.
With the MRS signal on, the inverter cannot be operated if the start signal is entered into the
inverter.
● Coast the motor to a stop.
When the start signal is turned off, the inverter decelerates the motor to a stop in the preset
deceleration time, but when the MRS signal is turned on, the motor coasts to a stop.
FR-E700 SC EC/ENE
Setting
Initial Value
Description
Range
0
Normally open input
Normally closed input (NC contact input
2
specifications)
0
External terminal: Normally closed input (NC
4
contact input specifications) Communication:
Normally open input
Motor coasts to
stop
Time
ON
ON
Function assignment of external terminals
Parameters referred to
178–184 Input terminal
function selection
Fig. 6-51:
Output shutoff signal
Refer to
Section
6.10.1
I001325C
6 - 119