Table 51: TXP-F13 SIB Alarm Messages

Alarm
Craft Interface
Type
Message
Red
SIB sib-number
Failure
SIB sib-number
Removed
SFC: SIB F13
sib-number VCSEL
fault
Yellow
Spare SIB Failure
Spare SIB
Removed
SIB
sib-numberconfig
mismatch
Copyright © 2010, Juniper Networks, Inc.
1.5 V
1.8 V
3.3 V
3.3 V bias
3.3 V ASF
9.0 V
SIB F2S 4/6 status:
State
Temperature
Power
1.2 V_1
1.2 V_ASF
1.2 V_ASF_B
1.2 V_ASF_D
1.5 V
1.8 V
3.3 V
3.3 V bias
3.3 V ASF
9.0 V
The text in the column labeled "LCD Message" appears in the display of the craft interface.
The text in the column labeled "CLI Message" appears in the output from the
command.
show chassis alarms
CLI Message
SIB sib-number Fault
SIB sib-number Absent
SFC: SIB F13 sib-number
VCSEL fault
Spare SIB Fault
Spare SIB Absent
SIB sib-numberconfig
mismatch
Chapter 21: Troubleshooting TX Matrix Plus Hardware Components
1511 mV
1820 mV
3306 mV
3306 mV
3318 mV
8265 mV
Online
33 degrees C / 91 degrees F
0 mV
1195 mV
1195 mV
1198 mV
1495 mV
1811 mV
3300 mV
3300 mV
3274 mV
8250 mV
Alarm Condition
Solution
A TXP-F13 SIB on an
Replace the TXP-F13 SIB or TXP-F2
active switching plane
SIB .
or a TXP-F2 SIB has
failed.
A TXP-F13 SIB on an
Reinstall the TXP-F13 SIB or TXP-F2
active switching plane
SIB in the chassis.
or a TXP-F2 SIB has
been removed.
A vertical-cavity
Replace the TXP-F13 SIB.
surface-emitting laser
(VCSEL) has failed.
A TXP-F13 SIB on a
Replace the TXP-F13 SIB.
backup switching plane
has failed.
A TXP-F13 SIB on a
Reinstall the TXP-F13 SIB.
backup switching plane
has been removed.
The TXP F13 SIB is
Remove TXP F13 SIB is installed from
installed in an
the unsupported slot, and install in a
unsupported slot.
supported slot.
303