Troubleshooting The Tx Matrix Plus Txp-Cips - Juniper TX MATRIX PLUS Hardware Manual

Hide thumbs Also See for TX MATRIX PLUS:
Table of Contents

Advertisement

Troubleshooting the TX Matrix Plus TXP-CIPs

Problem
Solution
Copyright © 2010, Juniper Networks, Inc.
During normal operation:
All TXP-CIPs are online.
The green
OK
LED on the faceplate of the TXP-CIP is lit.
The yellow
LED on the faceplate of the TXP-CIP is not lit.
FAIL
The following indicate a problem with a TXP-CIP:
The yellow
FAIL
LED on the faceplate of the TXP-CIP is lit.
The green
LED on the faceplate of the TXP-CIP is not lit.
OK
A TXP-CIPs is not online.
To troubleshoot the TXP-CIPs:
Check the LEDs on the TXP-CIP faceplate:
1.
Yellow
LED on the TXP-CIP faceplate is lit—Use the CLI for the status of the
FAIL
TXP-CIP.
Verify that the the TXP-CIP is
2.
command
cip sfc 0
user@host> show chassis environment cip sfc 0
CIP 0 status:
State
Temperature
Power 1
1.0 V
1.8 V
2.5 V
3.3 V
3.3 V bias
5.0 V
9.0 V
Bus Revision
CIP 1 status:
State
Temperature
Power 1
1.0 V
1.8 V
2.5 V
3.3 V
3.3 V bias
5.0 V
9.0 V
Bus Revision
Verify that the the links from the TXP-CIP to the T1600 routers (LCC) are
3.
the
command:
show chassis cip
user@host> show chassis cip
Chapter 21: Troubleshooting TX Matrix Plus Hardware Components
by issuing the issuing the
Online
Online Active
30 degrees C / 86 degrees F
1015 mV
1820 mV
2491 mV
3306 mV
3300 mV
5085 mV
9087 mV
74
Online Inactive
30 degrees C / 86 degrees F
1008 mV
1807 mV
2494 mV
3293 mV
3300 mV
5078 mV
8991 mV
74
show chassis environment
by issuing
Up
309