Appendix Ctx Matrix Plus Environmental Specifications; Tx Matrix Plus Router Environmental Specifications; Table 59: Tx Matrix Plus Router Environmental Specifications - Juniper TX MATRIX PLUS Hardware Manual

Hide thumbs Also See for TX MATRIX PLUS:
Table of Contents

Advertisement

APPENDIX C
TX Matrix Plus Environmental
Specifications

TX Matrix Plus Router Environmental Specifications

Copyright © 2010, Juniper Networks, Inc.
TX Matrix Plus Router Environmental Specifications on page 433
Table 59 on page 433 specifies the environmental specifications required for normal TX
Matrix Plus router operation. In addition, the site should be as dust-free as possible. Dust
can clog air intake vents, reducing cooling system efficiency. Check the vents frequently,
cleaning them as necessary.

Table 59: TX Matrix Plus Router Environmental Specifications

Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE: Install the TX Matrix Plus router only in restricted areas, such as
dedicated equipment rooms and equipment closets, in accordance with
Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA
70.
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping crate: –40°F (–40°C)
to 158°F (70°C)
Tested to meet Telcordia Technologies Zone 4 earthquake
requirements
15,559 BTU/hour (4560 W)
433

Advertisement

Table of Contents
loading

Table of Contents