Common Technical Data - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Technical data
D.1

Common technical data

Specifications
Test verification documents
Permiss. ambient temperature
In operation
For storage and transport
Site altitude above sea level
< 2000 m
< 3000 m
< 4000 m
Degree of protection
(according to IEC 60529)
All components (except current
measuring module with bus
connection, operator panel and door
adapter)
Current measuring module with
bus connection
Operator panel (front) and door
adapter (front) with cover
Shock resistance (sine pulse)
according to DIN EN 60068-2-27
Mounting position
Frequencies
EMC stability according to
• IEC 60947-1, IEC 60947-5-1,
SN 27095, NE21
• DM-F: IEC 61326-3-1
Conducted interference, burst
according to IEC 61000-4-4
Conducted interference, high
frequency according to
IEC 61000-4-6
Conducted interference, surge
according to IEC 61000-4-5
Electrostatic discharging,
ESD according to IEC 61000-4-2
Field-related interference according
to IEC 61000-4-3
D-2
EN 60204-1, EN 1760-1, DIN EN ISO 13849-1, IEC 61508
Certificates:
www.siemens.com/industrial-controls/approvals.
1)
-25 °C - +60 °C
2)
-40 °C - +80 °C
Max. +50 °C (no safe isolation)
Max. +40 °C (no safe isolation)
IP20
IP00
IP54
15 g / 11 ms
Any
50/60 Hz ± 5 %
Corresponds to Degree of Severity 3
2 kV (power ports)
overvoltage limiter is required
for inductive loads
1 kV (signal ports)
10 V
2 kV (line to earth)
1 kV (line to line)
8 kV (air discharge)
3)
6 kV (contact discharge)
10 V/m
.
SIMOCODE pro