Alarms, faults and system events
Event
Description
(alphabetical)
Status - DM-F
Shows the status of the
enabling circuit
enabling circuit:
• closed
or
• tripped
Status -
The thermal memory has been
Emergency start
deleted with the function
executed
"Emergency start".
Status - Test
The motor feeder is in the test
position (TPF)
position (TPF).
The main current circuit has
been interrupted and "cold
starting" of the feeder can be
carried out.
Temperature
The temperature warning level
module -
has been exceeded.
Warning level
exceeded
Temperature
Temperature sensor is delivering
module out of
impermissible values.
range
Temperature
Either a short circuit or an open
module sensor
circuit has occurred in the
fault
temperature sensor circuit.
Test position
Current is flowing in the motor
feedback (TPF)
feeder although the motor
feeder is in the test position
(TPF).
Test trip
The motor feeder has been
checked and switched off by a
test trip.
Thermistor open
An open circuit has occurred in
circuit
the thermistor sensor cable.
Thermistor short
A short circuit has occurred in
circuit
the thermistor sensor cable.
Thermistor trip
Thermistor protection response.
level
The temperature of the motor is
too high.
Trip antivalence
The limit switches are not
reporting any antivalent signals.
Table 15-1: Alarms, faults and system events (Cont.)
15-8
Troubleshooting
Acknowledg
ement/fault
rectification
The motor can be
switched on again
immediately after an
overload trip.
Check the temperature
measuring station.
Check the temperature
Reset
sensor.
Check the temperature
Rectify the
sensor and the sensor
fault; reset
cable.
The main circuit is not
Reset or
interrupted in test
OFF
operation.
command
Reset
Check the thermistor
Rectify the
sensor cable and the
fault; reset
thermistor.
Check the thermistor
Rectify the
sensor cable and the
fault; reset
thermistor.
Please check the motor
Reset, auto-
and the application that
reset
is being driven by the
motor.
The motor cannot be
switched on again until
the temperature has
reached the switch-back
point of the thermistor.
• Limit switch open
Counter
command
circuit
• Please check the
"OPEN/
positioner application
CLOSED"
and the limit switches
Contactor
Error
control
no.*)
17
35
Tripped
37
Tripped
36
Tripped
Tripped
65
Tripped
33
Tripped
32
Tripped
31
Tripped
16
SIMOCODE pro