Monitoring functions
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the
start-up procedure has been completed and there is no test position
feedback (TPF) (run+).
Response at trip level
Here you can set how SIMOCODE pro should respond if the set trip level is
undershot:
See also "Tables of responses of SIMOCODE pro" in
information".
Response
Deactivated
Signaling
Warning
Tripping
Delay
Table 5-9: "Trip level" response for cos phi monitoring
Response at warning level
Here you can set how SIMOCODE pro should respond if the warning level is
undershot:
See also "Tables of responses of SIMOCODE pro" in
information".
Response
Deactivated
Signaling
Warning
Tripping
Delay
Table 5-10: "Warning level" response for cos phi monitoring
5-12
Trip level
X
X
-
X
0 - 25.5 s (0.5 s)
Warning level
X
X
X
-
0 - 25.5 s (0.5 s)
Chapter "Important
Chapter "Important
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03