Data formats and data records
B.20
Data record 224 - Password protection
Description
• Password protection ON
If the data record is received with this control flag, the password protection is
activated and the password is accepted. If, at the time of receiving,
"Password protection ON" and the password are not the same, the event
"Event - Wrong password" is set and no change is carried out.
• Password protection OFF
If the data record is received with this control flag, the password protection
is deactivated. If the password is false, the event "Event - Wrong password" is
set and no change is carried out.
Byte.Bit
0.0
Reserved
4.0
Control flag: 0 = password protection OFF
4.1
Reserved
8.0
Password
16.0
Reserved
Table B-21: Data record 224 - Password protection