Technical Data - Siemens SSE161.05U Manual

Electromotoric actuator
Table of Contents

Advertisement

Technical data

Power supply
Operating voltage
Frequency
Power consumption
Primary fuse or breaker rating
Signal input
Control signal
Input impedance
Parallel operation (number of actuators)
Provided that the controller output is sufficient.
1)
Operating data
Position with de-energized contact Y
Running speed (time for 2.5 mm)
Positioning force
Stroke
Permissible temperature of medium in the connected
valve
Electrical connection
Permissible length for signal lines
Wire cross section
Cable diameter
Mounting
Connection to valve
Orientation
Standards
EU conformity declaration (CE)
RCM conformity declaration
UK conformity declaration (UKCA)
Housing protection degree
Protection class according to EN 60730
8
Siemens
Smart Infrastructure
AC 24 V (± 15 %) or DC 24 V (± 20 %)
50/60 Hz
3 VA (AC); 1.2 W (DC)
External, 2 A quick blow
DC 0...10 V
100 kOhm
Max. 10
1)
See "Technical design
[▶
2]"
< 5 s/mm ± 25 % (12.5 s ± 25 %)
45 lbf (200 N)
0.05 to 0.25 inch (1.2...6.5 mm)
34 to 248°F (1...120℃)
65 ft (20 m)
18...20 AWG (0.5...0.75 mm² )
<0.2 inch (5 mm)
Plastic coupling nut M30 × 1.5
Above horizontal
A5W00254962A
A5W00254983A
A5W00257055A
NEMA 2 / IP20 (EN 60529)
III
A6V12681514_enUS_b
06/15/2023

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ssf161.05u