Standard functions
10.4
External fault
Description
The "External Faults 1-6" function blocks can be used to monitor any
statuses and/or external devices, to generate fault messages and, if
necessary, to switch off the motor. To do this, the inputs (plugs) of the
"External Fault" function blocks must be connected to any sockets (e.g.
device inputs, control bits from PROFIBUS DP , etc.). External faults can also
be "marked" in SIMOCODE pro. This facilitates their allocation to the actual
malfunction. Example: Monitoring the rotational speed of the motor using
an external speed monitor.
The "External Fault" function block consists of:
• Two plugs (1 plug for setting, 1 plug for resetting)
• One "Event - External fault" socket. This is set when a signal is pending at the
input.
Overall, the following are available:
– Four "External Faults 1 to 4" function blocks for BU1
– Six "External Faults 1 to 6" function blocks for BU2.
Schematic
The following schematic shows the "External Fault" function blocks:
Input
Reset
Input
Reset
Input
Reset
Fig. 10-4: "External Fault" function blocks
10-10
External Fault 1
Type
Type
Event -
Ext. fault 1
Activity
Response
Reset
(Marking)
External Fault 3
Type
Type
Event -
Ext. fault 3
Activity
Response
Reset
(Marking)
External Fault 5
Type
Type
Event -
Ext. fault 5
Activity
Response
Reset
(Marking)
External Fault 2
Input
Type
Type
Activity
Response
Reset
Reset
(Marking)
External Fault 4
Input
Type
Type
Activity
Response
Reset
Reset
(Marking)
External Fault 6
Input
Type
Type
Activity
Response
Reset
Reset
(Marking)
GWA 4NEB 631 6050-22 DS 03
Event -
Ext. fault 2
Event -
Ext. fault 4
Event -
Ext. fault 6
SIMOCODE pro
Need help?
Do you have a question about the SIMOCODE pro and is the answer not in the manual?
Questions and answers