General - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Safety and commissioning information for EEx areas
F.1

General

Information and standards
Type of protection EEx e and EEx d:
The overload protection and thermistor motor protection of the
SIMOCODE pro system meets the requirements for overload protection of
explosion proof motors for the following types of protection:
• EExd "explosion proof enclosure", e.g. according to DIN EN 50018 or
DIN EN 60079
• EExe "increased safety", e.g. according to DIN EN 50019 or
DIN EN 60079-7.
Increased danger in hazardous areas means it is necessary to carefully
observe the following notes and standards:
• IEC 60079-14/EN 60079-14/DIN VDE 0165 - 1 Electrical apparatus for
explosive gas atmospheres - Electrical installations in hazardous areas (other
than mines)
• IEC 60079-17/EN 60079-17/DIN VDE 0165 - 10 - 1 Electrical apparatus for
explosive gas atmospheres - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• IEC 61241-14/DIN VDE 0165 - 2 Electrical apparatus for use in the presence
of combustible dust - Selection and installation
• IEC 61241-17/DIN VDE 0165 - 10 - 2 Electrical apparatus for use in the
presence of combustible dust - Inspection and maintenance of electrical
installations in hazardous areas (other than mines)
• VDE 0118 Erection of electrical installations in mines
• Betriebssicherheitsverordnung - BetrSichV (Ordinance on Industrial
Safety and Health).
All 3UF7 devices are approved under Device Group I, Category "M2" (mining)
and Device Group II, Category 2 in the area "GD" (areas in which explosive
gas, steam, fog, air mixtures and inflammable dust are present):
*) Note:
This safety and commissioning information is also valid for devices with the
certificate number BVS 04 ATEX F 003.
These devices are suitable for the protection of motors in hazardous areas
and comply with the standards listed above.
Tests other than those legally stipulated (Ordinance on Industrial
Safety and Health) are not required.
Warning
All installation, commissioning and maintenance work is to be carried out by
responsible, qualified personnel only. Unprofessional behavior can cause
serious damage to persons and goods.
F-2
BVS 06 ATEX F 001
BVS 06 ATEX F 001
I (M2) *)
II (2) GD *)
GWA 4NEB 631 6050-22 DS 03
SIMOCODE pro

Advertisement

Table of Contents
loading

Table of Contents