Control Station Settings - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

4.1.4

Control station settings

Control stations
LC
ON<<
ON<
OFF
ON>
ON>>
PLC/PCS [DP]
ON<<
ON<
OFF
ON>
ON>>
PC [DPV1]
ON<<
ON<
OFF
ON>
ON>>
Operator panel [OP]
<>/<<>>
ON<
OFF
ON>
ON>>
Mode selector
S1
S1
Table 4-3: Control station settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
Description
Activates the control station via an arbitrary signal
(arbitrary sockets
,
but usually device inputs).
The "OFF" plug is 0-active on the control station [LC].
Activates the control station via an arbitrary signal
(arbitrary sockets
,
but usually control bits from PROFIBUS DP)
Activates the control stations via an arbitrary signal
(arbitrary sockets
,
but usually control bits from PROFIBUS DPV1)
Activates the control stations via an arbitrary signal
(arbitrary sockets
,
but usually operator panel buttons)
For switching between the 4 operating modes Local 1,
Local 2, Local 3 and remote with arbitrary signals
(arbitrary sockets
, e.g. device inputs, control bits
from PROFIBUS DP , etc.)
Motor control
4-9

Advertisement

Table of Contents
loading