Positioner
ON <
OFF
ON >
FB ON
FC
FO
TC
TO
Non-maintained
command mode
Separate failsafe
function from
control function
Load type
Table 4-18: Positioner control function settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
definitions".
ON < control command (CLOSED)
(connection with arbitrary socket
usually with "Enabled control command - ON <" socket)
Control command STOP
(connection with arbitrary socket
usually with "Enabled control command - OFF" socket)
Control command ON > (OPEN)
(connection with arbitrary socket
usually with "Enabled control command - ON >" socket)
Auxiliary control input "Feedback ON"
(connection with arbitrary socket
usually with "Status - Motor current flowing" socket)
Auxiliary control input "Feedback CLOSED"
(connection with arbitrary socket
usually with the socket of an input to which the limit switch is
connected)
Auxiliary control input "Feedback OPEN"
(connection with arbitrary socket
usually with the socket of an input to which the limit switch is
connected)
Auxiliary control input "Torque CLOSED"
(connection with arbitrary socket
usually with the socket of an input to which the torque switch is
connected)
Auxiliary control input "Torque OPEN"
(connection with arbitrary socket
usually with the socket of an input to which the torque switch is
connected)
• Deactivated
• Activated
• Deactivated:
Safety-oriented tripping via the DM-F module also affects the
SIMOCODE pro control function, so that additional fault
messages are avoided.
This setting is selected for applications where safety-oriented
tripping directly affects the motor controlled by SIMOCODE pro.
• Activated:
Safety-oriented tripping via the DM-F module does not affect the
SIMOCODE pro control function.
This setting is selected for applications where safety-oriented
tripping does not affect the motor controlled by SIMOCODE pro.
You can choose between:
• Motor
• Resistive load (see
Chapter 4.2.2 "General settings and
definitions")